Skip to content
Product brief · PB-EVSE-SC-01 · rev 1.4 · September 2024

EVSE-SC-01 Shipped

Edge Load Balancer

First-generation site controller. Measures the main connection with three CT clamps and dynamically limits up to 4 Edge charge controllers over Modbus so the site never exceeds its main fuse. WiFi to the EdgeTech platform and the MyCharger app.

Edge Load Balancer EVSE-SC-01: light-grey DIN-rail module, three-quarter view showing the clamp inputs C1-C3
DIN-rail module, clamp inputs C1–C3
Edge Load Balancer EVSE-SC-01: terminal side with the RS485 bus (G, A+, B−), LED and supply terminals
Terminal side: RS485 bus, supply
Split-core current transformer supplied with the EVSE-SC-01: black clamp with the conductor opening and the direction arrow
One of the 3 split-core current transformers included, up to 40 A
Current transformer seen from above: the arrow shows the direction of current, the latches hold the clamp closed
Arrow: direction of current; the latches hold the clamp closed around the conductor

In short

A DIN-rail module for the distribution board that watches the main connection with three current clamps, supplied with it, and tells each charge controller, every second, how much current it may draw. Four charge points on a 3×25 A connection can all be plugged in; the load balancer splits what is left after the house or building has taken its share.

The module connects over WiFi to the EdgeTech platform, which gives users the MyCharger app (start/stop, off-peak charging, consumption overview, automatic invoicing) and gives installers remote diagnostics and firmware updates.

Price
€ 145 excl. VAT
CAD
STEP and drawing: edgetech.eu/cad/evse-sc-01.step

Key facts

SpecificationValue
Charge pointsUp to 4 EVSE-C-3x32A on one RS485 bus
Site measurement3 CT clamps on inputs C1, C2, C3: the household (mains) current per phase, up to 40 A per phase; CTs for higher currents on request
Modbus kWh meterOn request: EVSE-SC-01 with a DIN-rail Modbus kWh meter instead of the CT clamps, on the same Modbus cable as the charge controllers (for example where clamps don't fit in the cabinet)
Current transformers3 split-core CTs included; 23 × 40 × 26 mm (lid 14 mm), conductor opening 9 mm, 40 cm lead
Load balancingPer-second current limit per charge point, site limit configurable up to the main fuse, minimum 6 A per car, start threshold 8 A
FieldbusModbus RTU master, RS485, 9600 8N1
Bus cable3 × 0.75 mm² multi-core (stranded). No solid-core cable and no raw Ethernet cable in the terminals; Ethernet only with RJ45 connectors (adapter board on request)
ConnectivityWiFi IEEE 802.11 b/g/n, 2.4 GHz only; MQTT over TLS with a per-device pre-shared key
ModuleWiFi module (2.4 GHz)
Supply90–300 V AC, 50 Hz, 300 mA / 3 W, powered from the distribution board
Dimensions90 × 54 × 58 mm, DIN-rail enclosure (3 modules)
Enclosure ratingIP00, Class I; install inside the distribution board behind a fuse
CEEU declaration of conformity, site controller (2022-001): LVD, EMC, RoHS, EN 301 489-1/-17, EN 300 328, EN 62311
Made inEurope
Test it in your project: info@edgetech.euFull specifications: edgetech.eu/products/evse-sc-01